OPERATING PRINCIPLE The thermal mass sensor measures gas flow using two heated elements: one exposed directly to the flow, the other shielded. The gas in transit cools the active element, changing its electrical resistance. A digital circuit continuously rebalances the temperature of the two elements, providing a signal proportional to the mass of gas passing through the sensor. This technique eliminates errors due to pressure and temperature variations, directly returning flow in mass (kg/h) or standard volume (Nm³/h).

COMPETITIVE ADVANTAGES
▪ Direct mass measurement: eliminates compensation errors for reliable data in any condition.
▪ 100% digital design: advanced circuits and algorithms ensure stability and minimal drift over time.
▪ Wide measuring range: ratio up to 1:100, covers both extremely low and high flow rates.
▪ Hot-swap installation: extractable insert-type version for quick maintenance without stopping the plant.
▪ Plug & play integration: RS485 Modbus and HART for factory automation and real-time remote diagnostics.
▪ Industrial robustness: stainless steel construction, IP65 rating and ATEX certification for harsh environments.
TYPICAL APPLICATIONS
▪ Monitoring and control of technical gas flows (oxygen, nitrogen, compressed air, hydrogen)
▪ Dosing and mixing processes in chemical and pharmaceutical industries
▪ Combustion control systems and energy analysis
▪ Industrial air and gas treatment plants
▪ R&D and laboratory set-ups for precision flow measurements
| Technical data | |
| Parameter | Value |
| Diameter nominale | DN 25 – 3000 mm |
| Flow range | from 0,1 … 100 Nm³/s up to 16800 … 168000 Nm³/h (depending on diameter) |
| Accuratezza | typically ± 1% of full scale |
| Gas temperature | –20 … 250 °C |
| Nominal pressure | 1,0 … 4,0 MPa |
| Materials | Body in SS304/SS316; SS304 ball valve |
| Signal outputs | Impulsi; 4–20 mA; RS485 Modbus; HART |
| Unit of measure | Nm³/h, Nm³/min, NL/h, NL/min, t/h, t/min, kg/h, kg/min |
| Power in | 24 V DC + 220 V AC |
| Connections | Flanged (DN 15–400 mm); insert type (DN 65–3000 mm) |
| Protection | IP65 |
| Certification ATEX | Ex d IIC T6 Gb |
| DN (mm) | Gas thermal flow rate (Nm³/h) |
| DN10 | 1,7 - 17 |
| DN15 | 4 - 40 |
| DN20 | 6 - 60 |
| DN25 | 10 - 100 |
| DN32 | 17 - 170 |
| DN40 | 27 - 270 |
| DN50 | 36 - 360 |
| DN65 | 72 - 720 |
| DN80 | 108 - 1080 |
| DN100 | 168 - 1680 |
| DN125 | 264 - 2640 |
| DN150 | 378 - 3780 |
| DN (mm) | Gas thermal flow rate (Nm³/h) |
| DN200 | 600 - 6000 |
| DN250 | 1000 - 10000 |
| DN300 | 1500 - 15000 |
| DN350 | 2100 - 21000 |
| DN400 | 2700 - 27000 |
| DN450 | 3420 - 34200 |
| DN500 | 4200 - 42000 |
| DN600 | 6000 - 60000 |
| DN700 | 8100 - 81000 |
| DN800 | 10800 - 108000 |
| DN900 | 13800 - 138000 |
| DN1000 | 16800 - 168000 |
20092 Cinisello Balsamo (MI), Via dei lavoratori, 15-19